Thermasolv CF1 is a dielectric heat transfer fluid from Inventec Performance Chemicals. It is built for single-phase immersion and direct cooling, so electronics can run under power while fully submerged.
Key Features of Thermasolv CF1
- Boiling point 170°C / 338°F
- Dielectric strength over 40 kV
- Perfect for single-phase immersion
What Is Thermasolv CF1 Used For?
Typical uses include single-phase immersion cooling and cold plate or tube direct cooling. It also suits dielectric testing and specialised manufacturing cooling.
A Wide Operating Range
A high boiling point of 170°C and a low pour point of -100°C give an operating range of -100°C to 160°C. As a result, one fluid covers both very cold and very hot duty cycles.
Efficient Heat Transfer
Thermal conductivity of 0.111 W/m-K and low surface tension help draw heat away from components. Meanwhile, low kinematic viscosity (1.81 cSt at 20°C) keeps strain on pumps to a minimum.
Is Thermasolv CF1 Safe With Live Electronics?
Yes. Its dielectric strength is over 40 kV, with resistivity of 1.00E+13 Ohm-cm. Therefore, equipment can keep running under power while fully submerged. It is also non-flammable, with no flash point, and non-toxic.
Why Choose Thermasolv CF1?
It is thermally and chemically stable, with zero ozone depletion potential. In addition, you can recycle used fluid through Inventec’s Ecoprogram service. So it is a reliable, cost-efficient choice for demanding cooling systems.
Thermasolv CF1 Technical Specifications
| Specification | Value |
|---|---|
| Appearance | Colorless, Clear |
| Purity | >99.5% |
| Flash Point | None |
| Boiling Point | 170°C / 338°F |
| Pour Point | -100°C / -148°F |
| Critical Temperature | 300°C / 572°F |
| Vapor Pressure (@20°C) | 0.1 kPa |
| Liquid Density (@20°C) | 1770 kg/m³ |
| Kinematic Viscosity (@20°C) | 1.81 cSt |
| Specific Heat (@25°C) | 1026 J/kg-K |
| Surface Tension | 17 dynes/cm |
| Thermal Conductivity | 0.111 W/m-K |
| Water Content Spec | 15 ppm |
| Water Solubility in Fluid | <14 ppm (weight) |
| Dielectric Strength | >40 kV |
| Dielectric Constant (@1kHz) | 1.84 |
| Resistivity | 1.00E+13 Ohm-cm |
| Ozone Depletion Potential (ODP) | None |
| Operating Range (1-Phase) | -100°C to 160°C |
Browse our full range of cooling fluids to compare options for your application.