Thermasolv CF6 is a dielectric heat transfer fluid from Inventec Performance Chemicals. It is built for single-phase immersion and direct cooling at higher operating temperatures.

Key Features of Thermasolv CF6

  • Boiling point 158°C / 316°F
  • Dielectric strength 40 kV
  • Perfect for high-temperature cooling

What Is Thermasolv CF6 Used For?

Typical uses include single-phase immersion cooling, cold plate or tube direct cooling and dielectric testing. It also suits specialised manufacturing cooling.

Built for Higher Temperatures

A boiling point of 158°C supports an operating range of -20°C to 148°C. In addition, a pour point of -60°C and low kinematic viscosity (3.0 cSt at 20°C) keep pump strain low.

Is Thermasolv CF6 Safe With Live Electronics?

Yes. Its dielectric strength is 40 kV, with resistivity above 1.00E+11 Ohm-cm. Therefore, equipment can run under power while submerged. It is also non-flammable and non-toxic, with no EUH-phrase hazard classifications.

Also a Soldering Aid

As well as cooling, it can serve as a tacky agent for preform die-attach soldering. Meanwhile, thermal conductivity of 0.066 W/m-K and low surface tension (17 dynes/cm) support efficient heat transfer.

Why Choose Thermasolv CF6?

It is thermally and chemically stable, with a low GWP of 180 and zero ODP. You can also recycle used fluid through Inventec’s Ecoprogram service. So it is a cost-efficient choice for higher-temperature cooling.

Thermasolv CF6 Technical Specifications

Specification Value
Appearance Colorless, Clear
Purity >99.5%
Flash Point None
Boiling Point 158°C / 316°F
Pour Point -60°C / -76°F
Vapor Pressure (@20°C) 3.7 kPa
Liquid Density (@20°C) 1810 kg/m³
Kinematic Viscosity (@20°C) 3.0 cSt
Specific Heat (@25°C) 1151 J/kg-K
Surface Tension 17 dynes/cm
Thermal Conductivity 0.066 W/m-K
Dielectric Strength 40 kV
Dielectric Constant (@1kHz) 4.75
Resistivity >1.00E+11 Ohm-cm
Ozone Depletion Potential (ODP) None
Global Warming Potential (GWP) 180
Operating Range -20°C to 148°C

Browse our full range of cooling fluids to compare options for your application.

You may also like…

Series 86xx Wire Bonder
thermasolv

Thermasolv CF4

  • • Boiling point: 98°C
  • • Dielectric strength: 40kV
  • • Perfect for semiconductor cooling
thermasolv

Thermasolv CF5

  • • Boiling point: 110°C
  • • Ultra-low GWP: 2.5
  • • Ideal for semiconductor cooling
Rehm X-Line In-Line Vapor Phase System

Thermasolv CF6

In Stock

  • Dielectric heat transfer fluid dedicated to 1-phase immersion and direct cooling systems
  • Colorless, clear liquid with >99.5% purity
  • Non-flammable with no flash point, and non-toxic with no EUH-phrase hazard classifications
  • Ultra-low Global Warming Potential (GWP of 180) and zero ozone depletion potential (ODP)
  • High boiling point (158°C/316°F) supporting a wide operating range of -20°C to 148°C
  • Low pour point (-60°C/-76°F) and low kinematic viscosity (3.0 cSt @20°C), minimizing pump strain
  • High dielectric strength (40 kV) and resistivity (>1.00E+11 Ohm-cm), providing superior electrical insulation for equipment run under power while submerged
  • Excellent thermal conductivity (0.066 W/m-K) and low surface tension (17 dynes/cm²) for efficient heat transfer
  • Thermally and chemically stable, supporting cost-efficient long-term performance
  • Can also serve as a tacky agent for preform die-attach soldering applications
  • Recyclable through the ECOPROGRAM service for reuse and reduced environmental impact
  • Suitable for single-phase immersion cooling, cold plate/tube direct cooling, dielectric testing, and specialized manufacturing cooling applications

Technical Specifications

Specification Value
Appearance Colorless, Clear
Purity >99.5%
Flash Point None
Boiling Point 158°C / 316°F
Pour Point -60°C / -76°F
Vapor Pressure (@20°C) 3.7 kPa
Liquid Density (@20°C) 1810 kg/m³
Kinematic Viscosity (@20°C) 3.0 cSt
Specific Heat (@25°C) 1151 J/kg-K
Surface Tension 17 dynes/cm²
Thermal Conductivity 0.066 W/m-K
Dielectric Strength 40 kV
Dielectric Constant (@1kHz) 4.75
Resistivity >1.00E+11 Ohm-cm
Ozone Depletion Potential (ODP) None
Global Warming Potential (GWP) 180
Operating Range -20°C to 148°C